HTC-PX/HX
Self-regulating heating cable for ATEX environments
for temperatures up to 85ºC (class T6)
DISCOVER THE RANGE
APPLICATIONS
- Industrial applications of pipe freeze protection, and heating or maintaining process temperature of pipes, tanks and vessels up to 85 ºC
- Certified for use in potentially explosive atmospheres (ATEX II 2 GD)
FEATURES
- Degree of protection: IP 66 (EN 60529)
- CE Marking
Type
Self-adjusting
Supply voltage
230 Vac
Conductor cross-section
1.3 mm2 (16 AWG)
Maximum intermittent exposure temperature
85 ºC (IECEx T6)
Maximum continuous operating temperature
65 ºC
Cable cross-sectional dimensions
12.8 × 6.3 mm
Minimum bending radius
40 mm (at -40ºC)
ATEX Classification Ex II 2 GD | |
FM18ATEX0062X | |